Experimental analysis of bolts employed as shear connectors in circular concrete-filled tube columns.
Nenhuma Miniatura Disponível
Data
2019
Título da Revista
ISSN da Revista
Título de Volume
Editor
Resumo
This paper presents experimental and theoretical analysis of bolts employed as shear connectors in circular concrete-filled steel tube columns
(CFTs). The theoretical results, obtained from ABNT NBR 16239:2013 formulations, were compared with the experimental results. A series of
push-out tests were carried out, where the diameter and length of the bolts, the number of connectors and the concrete strength were varied.
From the experimental results, it was observed that the equations from ABNT NBR 16239:2013 are conservative. Therefore, it is proposed an
adjustment to the formulations in order to consider the concrete confinement. It was also verified that increments in the diameter and the length
of the bolt increase the load capacity of the connector. However, the variation of the quantity of bolts and the concrete strength did not interfere
in the load capacity.
Descrição
Palavras-chave
Circular tubular section, Seção tubular circular
Citação
XAVIER, E. M. et al. Experimental analysis of bolts employed as shear connectors in circular concrete-filled tube columns. Revista IBRACON de Estruturas e Materiais, São Paulo, v. 12, n. 2, p. 337-370, abr. 2019. Disponível em: <http://www.scielo.br/scielo.php?pid=S1983-41952019000200337&script=sci_arttext>. Acesso em: 10 mar. 2020.